If a GRANITE™VWIRE 305 system is running and there are skipped scans in the data logger, what can be done?

The CPI bus speed is adjustable in your CRBasic data logger program. Use the CPISpeed() instruction in your CRBasic program to adjust the CPI bus bandwidth to meet the following maximum combined (total) Ethernet cable lengths:

  • 1000 kB/s for maximum combined Ethernet cable lengths of 15.2 m (50.0 ft)
  • 500 kB/s for maximum combined Ethernet cable lengths of 61 m (200 ft)
  • 250 kB/s for maximum combined Ethernet cable lengths of 152.4 m (500 ft)